COLUMBIA BOILER CO. OF POTTSTOWN
POTTSTOWN, PENNSYLVANIA 19464
EMERALD SERIES
EM-85 THRU EM-200
OIL FIRED PACKAGED BOILER BURNER UNIT
INSTALLATION AND OPERATORS MANUAL
COLUMBIA
®
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - COLUMBIA

COLUMBIA BOILER CO. OF POTTSTOWNPOTTSTOWN, PENNSYLVANIA 19464EMERALD SERIESEM-85 THRU EM-200OIL FIRED PACKAGED BOILER BURNER UNITINSTALLATION AND OPE

Page 2 - FLUE BOX

7Troubleshooting GuideTROUBLE: BURNER DOES NOT STARTSOURCE PROCEDURE CAUSES REMEDYPower Check boiler disconnect Switch open. Close switch.and main di

Page 3 - Homeowner / Installer Policy

8TROUBLE: BURNER STARTS BUT DOES NOT ESTABLISH FLAMESOURCE PROCEDURE CAUSES REMEDYOil Supply Check tank for oil Empty tank. Fill tank.Check for water

Page 4 - COLUMBIA BOILER CO

9TROUBLE: BURNER FIRES, BUT THEN FAILS ON SAFETYSOURCE PROCEDURE CAUSES REMEDYCad Cell Check cad cell with ohmmeter. Faulty or dirty cad cell Clean o

Page 5

10TROUBLE: BURNER FIRES BUT PULSATESSOURCE PROCEDURE CAUSES REMEDYDraft Take a draft reading. Draft Insufficient draft Increase draft setting. Besho

Page 6

11TROUBLE: INSUFFICIENT HEATSOURCE PROCEDURE CAUSES REMEDYCirculator Check if circulator is Pump binding Replace pumpoperational.Circulator motor bur

Page 7

12ELECTRICAL DIAGRAM FOR EM SERIES BOILERSTO CONNECT BURNER TO AQUASTAT(APPLIES TO CARLIN CHIMNEY VENT AND RIELLO CHIMNEY VENT BURNERS)

Page 8

13ELECTRICAL DIAGRAM FOR EM SERIES BOILERSTO CONNECT BURNER TO AQUASTAT(APPLIES TO BECKETT CHIMNEY VENT BURNERS)

Page 9 - FIGURE 1

14123451. Date2. Model Number3. Firing Rate4. Pump Pressure*5. CO26. “0” Smoke7. Gross Stack°F8. Draft Over Fire9. Replaced Filter Yes/No10. Replaced

Page 10 - Troubleshooting Guide

156789101. Date2. Model Number3. Firing Rate4. Pump Pressure*5. CO26. “0” Smoke7. Gross Stack°F8. Draft Over Fire9. Replaced Filter Yes/No10. Replaced

Page 11

16Columbia Emerald Boiler/BurnerUnit SpecificationsPump Burner Delavan Approximate Air SettingBoiler Model Pressure PSI Hd. Nozzle Shutter BandEM - 85

Page 12

FLUE BOX

Page 13 - TROUBLE: TOO MUCH HEAT

CBC P/N 59585010/08 - 500CC-7821OIL BURNERBECKETT AFG BURNER (PART NO. 540120)CARLIN EZ-1 BURNER (PART NO. 542210)RIELLO F-5 BURNER (PART NO. 541152)N

Page 14 - TROUBLE: INSUFFICIENT HEAT

TABLE OF CONTENTSPageEmerald Series Boiler Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Installation and

Page 15 - TO CONNECT BURNER TO AQUASTAT

1IBR/DOE RATINGS AND DATABoiler Model No. EM-85 EM-100 EM-3100 EM-110 EM-125 EM-3125 EM-135 EM-150 EM-165 EM-175 EM-200Firing Rate -- #2 Fuel .85 1.00

Page 16

2Emerald Series Installation and Operators ManualCOLUMBIACOLUMBIA BOILER CO. OF POTTSTOWNBox G, Pottstown, Pennsylvania 19464A Message to: Installer

Page 17 - BURNER SERVICE SET-UP RECORDS

3Relief valve discharges and drain valve pip-ing should be piped to a safe place of dis-charge. All plugs and water connectionsshould be checked for l

Page 18

4f) A dangerous combustion condition, allow-ing the firebox to fill with a lean mixture (too much air in the oil stream) which could cause a delay in

Page 19 - Unit Specifications

52) In order to take flue gas samples for com-bustion testing a 1/4" hole must be drilled in the flue pipe between the boiler and the barometric